Home > Control Valves > Motorised Control Valves > 5516A-CSF |
| |
|
2/3-Way Motorised Control Valves with Electric Actuator
For Thermic
Fluid Application-Mixing or Diverting Type
(On-Off and Control Application) |
DATA SHEET
MV-5516A/WCBF |
|
| |
|
| SPECIFICATIONS : |
| Sizes |
20mm (3/4”) to 150mm (6”). |
| Unified Flanges |
As per ANSI CI. 150 and PN 16. |
| Pressure Rating |
As per ANSI CI. 150,CI. 300, PN 16 & PN 25. |
| Pressure Temp. rating |
As per ASTM-A-16.34. |
| Gland Packing |
Carbon filled Teflon for temp. upto 420°C with Cooling Finned Bonnet. |
| Design Standard |
ASME B16.34. |
| Leakage |
As per ASME 16.104 CI.IV (0.01% of Kv). |
| Face to Face |
As per DIN-3202. Part I Series F1. (All materials) |
| Testing Standard |
As per ISA S 7501. |
| Type of Plug |
On-Off or Linear. |
| Seat |
Screwed type replaceable. |
| Body & Bonnet Material |
CS-ASTM A 216 WCB (DIN 1.0619 GS-C 25).
SG Iron-ASTM A536,Gr.60-40-18 (DIN 0.7043) (GGG40.3). SS-ASTM A351CF8M (DIN1.4408)
(GX6 Cr.Ni MO 1810) SS-ASTM A351 CF8 (DIN1.4301) |
| Plug Material |
SS AISI 420/316. |
| Seat Ring |
SS AISI 420/316. |
| Spindle |
410/316 Ground, Burnished & Hard Chromed. |
| Studs |
ASTM A193 Gr. B7. |
| Hex. Nuts |
ASTM A194 Gr. 2H. |
| Body Packing |
Cr.Ni Foil coated with graphite. |
| Rangeability |
Linear 50:1. |
| Fluid |
Hot Thermic Fluid, Hot Water, Hot Steam, etc. |
| Note |
5516A are Metal Seated Valves. |
|

|
| ACTUATOR : |
| Electric Actuator |
Series KN. |
| Housing |
Aluminium Silicon alloy heat treated. |
| Gears |
Steel hobbed, toughened gears. |
| Electric Motor |
Single phase, permanent split phase capacitor type class ‘F’ insulated motor. |
| Electric Supply |
220/240,110,24 Volts 50/60 Hz, AC. |
| Switching cycles |
Upto 240 cys per hour for small size valves and for large size valves refer to AVCON.
(Switching cycles is meant for duration of less than 0.1 second). |
| Actuator Yoke |
Steel rods with position indicator assembly or Cast Carbon Steel casting. |
| Stem Tension |
Through belleville packed spring. |
Valve Position on
Failure of Electricity. |
Stayput |
| Control Suitability |
Actuator is suitable for On-Off, Anticipatory, PI, PID Control system. |
| For further details of Actuator refer to Actuator leaflet KN’ series. |
|
|
| |
| SPECIFICATION TABLE |
Catalogue
Number |
Size |
Orifice
Size |
Flow
Factor
Kv |
Safe
Working
Pressure |
Actuator |
Stroke
(Approx.) |
Travel
time
(Approx.) |
| KN-02 |
KN-05 |
KN-10 |
KN-25 |
| (mm) |
(mm) |
M³/hr. |
Bar |
Working Pressure (Bar) |
mm |
Secs. |
| 5516A205/WCBF x KN 02/05 |
20 |
22 |
6.3 |
40 |
15 |
40 |
- |
- |
20 |
49 |
| 5516A255/WCBF x KN 02/05 |
25 |
25 |
10 |
40 |
12 |
35 |
- |
- |
20 |
48 |
| 5516A405/WCBF x KN 02/05 |
40 |
40 |
25 |
40 |
10 |
20 |
- |
- |
20/30 |
48 |
| 5516A505/WCBF x KN 05/10 |
50 |
50 |
40 |
40 |
- |
15 |
40 |
- |
30 |
80 |
| 5516A655/WCBF x KN 05/10 |
65 |
65 |
63 |
40 |
- |
7 |
30 |
- |
30 |
80 |
| 5516A805/WCBF x KN 10 |
80 |
80 |
100 |
40 |
- |
- |
20 |
- |
30 |
60 |
| 5516A1005/WCBF x KN 10/25 |
100 |
100 |
160 |
40 |
- |
- |
12 |
20 |
30 |
60 |
| 5516A1505/WCBF x KN 10/25 |
150 |
150 |
320 |
40 |
- |
- |
5 |
10 |
50 |
100 |
|
| |
|
|
|
|
|
| 2/3 WAY FINNED BONNET PNEUMATIC CONTROL VALVES WITH ELECTRIC ACTUATOR |
| |
| BILL OF MATERIAL |
| Item |
Parts |
Material |
| 1 |
Body |
SS ASTM A351CF8/CF8M |
| CS ASTM A216, Gr. WCB |
| CI, SGI |
| 2 |
Seat |
SS AISI 420/ SS AISI 316 |
| 3 |
Gasket |
Foil coated with Cr. Ni.Graphite |
| 4 |
Plug |
SS AISI 420/ SS AISI 316 |
| 5 |
Duro Bush |
PTFE Lined & coated, |
| SS as backed. |
| 6 |
Bonnet |
SS ASTM A351CF8/CF8M |
| CS ASTM A216, Gr. WCB |
| CI, SGI |
| 7 |
Studs/ Nuts |
IS 1363, ASTM A193, Gr.B7 |
| IS 1363, ASTM A 194 Gr.2H |
| 8 |
Gland Packing |
Graphited PTFE |
| 9 |
Gland Nut |
SS AISI 304 |
| 10 |
Yoke Nut |
CS ASTM A216, Gr. WCB |
| 11 |
Actuator |
Electric Actuator* |
|
 |
| *Refer to actuator leaflet for details of components. |
|
| |
| TECHNICAL DATA TABLE |
| Valve Size in mm |
20 |
25 |
40 |
50 |
65 |
80 |
100 |
150 |
| 5516 Mixing |
Port size |
Upper ‘A’ Port |
21 |
27 |
40 |
50 |
65 |
80 |
101 |
140 |
| Dim. in mm |
Lower ‘B’ Port |
25 |
27 |
40 |
50 |
60 |
75 |
95 |
140 |
Kv
M³/hr. |
6.3 |
10 |
25 |
40 |
63 |
100 |
160 |
320 |
| Travel |
20 |
20 |
20 |
30 |
30 |
30 |
30 |
30 |
| 30 |
30 |
30 |
50 |
Electric
Actuator |
KN 02 |
KN 02 |
KN 02 |
KN 05 |
KN 05 |
KN 10 |
KN 10 |
KN 10 |
| KN 05 |
KN 05 |
KN 05 |
KN 10 |
KN 10 |
KN 25 |
KN 25 |
|
| |
| DIMENSIONS (IN MM) |
Catalogue
Number |
Size |
Electric
Actuator |
A |
B |
C |
F x G
or
ØD |
Wt.Kg.
(Approx.) |
Envelop Size
L x H x W
(Approx.) |
Box Wt.
Kg.
(Approx.) |
| Inch |
| 5516A205/WCBF x KN 02 |
3/4 |
KN 02 |
150 |
70 |
553 |
215 x 142 |
10.0 |
673 x 240 x 167 |
12.5* |
| 5516A201/WCBF x KN 05 |
KN 05 |
580 |
Ø178 |
700 x 203 x 203 |
13.5* |
| 5515A255/WCBF x KN 02 |
1 |
KN 02 |
160 |
75 |
608 |
215 x 142 |
12.5 |
733 x 240 x 167 |
14.5* |
| 5516A251/WCBF x KN 05 |
KN 05 |
635 |
Ø178 |
760 x 203 x 203 |
16.0* |
| 5516A405/WCBF x KN 02 |
1 ½ |
KN 02 |
200 |
90 |
621 |
215 x 142 |
19.0 |
761 x 240 x 167 |
23.0* |
| 5516A401/WCBF x KN 05 |
KN 05 |
650 |
Ø178 |
790 x 203 x 203 |
24.0* |
| 5516A505/WCBF x KN 05 |
2 |
KN 05 |
230 |
100 |
730 |
Ø178 |
27.0 |
880 x 203 x 203 |
32.0* |
| 5516A501/WCBF x KN 10 |
KN 10 |
835 |
Ø225 |
33.0 |
985 x 250 x 250 |
39.0* |
| 5516A655/WCBF x KN 05 |
2 ½ |
KN 05 |
290 |
145 |
755 |
Ø178 |
36.0 |
950 x 203 x 203 |
43.0** |
| 5516A651/WCBF x KN 10 |
KN 10 |
855 |
Ø225 |
45.0 |
1050 x 250 x 250 |
54.0** |
| 5516A805/WCBF x KN 05 |
3 |
KN 10 |
310 |
155 |
925 |
Ø225 |
56.0 |
1130 x 250 x 250 |
65.0** |
| 5516A1005/WCBF x KN 10 |
4 |
KN 10 |
350 |
175 |
930 |
Ø225 |
75.0 |
1155 x 250 x 250 |
86.0** |
| 5516A 1001/WCBF x KN 25 |
KN 25 |
1012 |
Ø260 |
89.0 |
1237 x 285 x 285 |
90.0** |
| 5516A1505/WCBF x KN 10 |
6 |
KN 10 |
480 |
225 |
988 |
Ø225 |
103.0 |
1263 x 250 x 250 |
110.0** |
| 5516A1501/WCBF x KN 25 |
KN 25 |
1070 |
Ø260 |
107.0 |
1345 x 285 x 285 |
120.0** |
|
| Note: |
| * Weight of cardboard + PUF Box Packing. Which may change for Export when packed in wooden box.** Weight of Wooden Box Packing. |
| |
| Note: |
Technical specifications details & dimensions are subject to change without prior notice.
Dimensions in the table are approximate subject to final confirmation by AVCON. |
|
|
|
|
|
|
|