2/2- Way Direct Acting Solenoid Valve
for steam and hot water application upto 4 bar pressure
Normally Closed, Energised To Open
|
DATA SHEET
9130 B |
|
| |
| SPECIFICATIONS : |
| Sizes |
6mm (1/4") to 15mm (1/2"). |
| End Connections |
Standard-BSP. |
| Construction-Body |
Upto 6mm (1/4") Brass forged IS 6912 and above in
SS ASTM A351 Gr. CF8 or CF8M. |
| Seat |
EPDM. |
| Differential Pressure |
From 0 to 4 bar (See table). |
| Coil Voltage |
Standard-230-volts, 50Hz AC.
Optional-Any Standard AC range. |
| Coil Insulation and Temperature |
Ambient upto 42°C.
Class 'H' insulated upto 155°C.
Class 'C' insulated upto 180°C. |
Coil rating
|
Continuously rated. |
| Enclosure |
Standard-General Purpose SQ. moulded coil upto IP-20,
Optional- Weatherproof SQ. moulded coil upto IP-67, Flameproof Round coil upto FLP IIB / FLP IIC. |
| Approvals |
CMRS Dhanbad. |
| Fluids |
Steam temp. upto 150°C.
Hot water temp. upto 95°C. |
| Sales Point |
Direct acting, standard valve for low pressure steam application. |
| Application |
Steaming equipment, textile, processing equipment, laundry equipments, kitchen equipment and others. |
|
 |
| Note |
Not suitable for back pressure from out let side.
Hot water temperature limited upto 95°C only.
Suitable for wet steam:
Not available in Normally Open Design.
Not available in DC Construction.
Not available with MO.
For high pressure steam, use valve type 9130H.
For instruction manual refer IM 9130.
USE OF FILTER IN THE INLET SIDE IS HIGHLY RECOMMENDED. |
|
|
|
| |
SPECIFICATION TABLE

2/2 WAY NORMALLY CLOSED |
Catalogue
Number |
pipe
Size |
Orifice
Size |
Flow Factor
Kv |
Minimum
pressure |
Maximum Operating Pressure
(bar) |
BTP |
Material |
Constr.
Ref. |
VA
Rating |
Coil |
Housing |
| Inch |
mm |
M³/hr. |
bar |
Hot Water* |
Steam |
bar |
Body |
Seat |
AC |
Type |
| 9130B61 |
1/4 |
6 |
0.80 |
0 |
4 |
4 |
40 |
BR |
EPDM |
157 |
36 |
M50-HT |
SQ |
| 9130B6110 |
3/8 |
6 |
0.80 |
0 |
4 |
4 |
40 |
CF8 |
EPDM |
158 |
36 |
M50-HT |
SQ |
| 9130B6115 |
1/2 |
6 |
0.80 |
0 |
4 |
4 |
40 |
CF8 |
EPDM |
158 |
36 |
M50-HT |
SQ |
| 9130B8115 |
1/2 |
8 |
1.30 |
0 |
1.5 |
1.5 |
40 |
CF8 |
EPDM |
158 |
36 |
M50-HT |
SQ |
| 9130B1115 |
1/2 |
11 |
2.00 |
0 |
0.6 |
0.6 |
40 |
CF8 |
EPDM |
158 |
36 |
M50-HT |
SQ |
|
| * Hot water at 95°C only. |
| |
| ELECTRICAL REFERENCE |
| Coil Type |
Power Consumption & Watt Rating |
Class Of
Insulation |
Protection |
| AC |
| VA
Inrush |
VA
Holding |
| M 50 HT SQ |
50 |
36 |
H |
C |
GP/WP IP-67 |
| M 50 HT RD |
50 |
36 |
H |
C |
GP/WP IP-67 |
| M 50 HT
FLP IIB/FLP IIC |
50 |
36 |
H |
C |
IS 2148 Group IIA, IIB, IIC
IS 13947 Part I IP-67
IS 4012 Dustproof/ IS 4013 Dustlight |
|
|
| DIMENSIONS ( IN MM ) |
Catalogue
Number |
Pipe
Size |
Constr.
Ref. |
A |
B |
C |
Weight
(Approx.) |
| Inch |
kgs.* |
| 9130B61 |
1/4 |
157 |
39.5 |
10.5 |
98 |
0.615 |
| 9130B6110 |
3/8 |
158 |
54 |
16 |
107 |
0.735 |
| 9130B6115 |
1/2 |
158 |
54 |
16 |
107 |
0.735 |
| 9130B8115 |
1/2 |
158 |
54 |
16 |
107 |
0.735 |
| 9130B1115 |
1/2 |
158 |
54 |
16 |
107 |
0.735 |
|
| * Weight with SQ enclosure only, ask AVCON for other weights. |
|
| |
| FLOW CALCULATION GRAPHS FOR SATURATED STEAM : |
| The valve flow coefficient Kv = 1, if 1 cubic meter (m³) water (at 30°C) is passing through the valve per hour with a pressure drop (∆P) of a bar. To select the right valve with certain Kv value, read to steam flow graphs as follows. |
| |
| EXAMPLE : |
| A valve is required to pass 400 Kg/h (Qm) of saturated steam at inlet pressure of 7 bar (g) ∆P of 0.5 bar : What is the Kv? |
| |
| SOLUTION : |
| Read the steam graph to find the graph factor (Fg) and use the formula : Kv=QM/Fg = 400/45 = 8.5 |
| |
| NOTE : |
| Absolute pressure = gauge pressure plus atmospheric pressure of 1.033 bar. In most system it is desirable to keep the pressure drop to a minimum. Never use a ∆P greater than 50% of the absolute inlet pressure because excessive pressure drop cause irregular flow. |
| |
| Note: |
Technical specifications details & dimensions are subject to change without prior notice.
Dimensions in the table are approximate subject to final confirmation by AVCON. |
| |
|
|
|
|