Home > Solenoid Valves > 2 Way Solenoid Valves for Steam & Hot Water > 9130D |
|
| |
2/2-Way Pilot Operated, Diaphragm Type, Solenoid Valves
For steam and hot water application upto 4 bar pressure,
Normally Closed, Energised To Open |
DATA SHEET
9130 D |
|
| |
|
| SPECIFICATIONS : |
| Sizes |
10 mm (3/8") to 50 mm (2"). |
| End Connections |
Standard-BSP. |
| Construction-Body |
Upto 20mm (3/4") Brass forged IS 6912 and above in
SS ASTM A351 Gr. CF8 or CF8M. |
| Diaphragm-Seat |
Standard EPDM. |
| Differential Pressure |
From 0.5 to 4 bar (See table). |
| Coil Voltage |
Standard-230-volts, 50Hz AC.
Optional-Any Standard AC range. |
| Coil Insulation and Temperature |
Ambient upto 42°C.
Class 'H' insulated upto 155°C.
Class 'C' insulated upto 180°C. |
Coil rating
|
Continuously rated. |
| Enclosure |
Standard-General Purpose SQ. moulded coil upto IP-20,
Optional- Weatherproof SQ. moulded coil upto IP-67,
Flameproof Round coil upto FLP IIB/ FLP IIC. |
| Approvals |
CIMFR Dhanbad. |
| Fluids |
Steam temp. upto 150°C.
Hot water temp. upto 95°C. |
| Sales Point |
Diaphragm pilot operated, standard valve for low pressure steam application. |
| Application |
Steaming equipment, textile, processing equipment, laundry equipment, kitchen equipment and others. |
|
 |
| Note |
Not suitable for back pressure from out let side.
Hot water temperature limited upto 95°C only.
Suitable for wet steam:
Not available in Normally Open Design.
Not available in DC Construction.
For high pressure steam, use valve type 9130H.
For instruction manual refer Gen IMSV & Gen
IM coils.
Manual override not available.
USE OF FILTER IN THE INLET SIDE IS HIGHLY RECOMMENDED. |
|
|
|
 |
SPECIFICATION TABLE

2/2 WAY NORMALLY CLOSED |
Catalogue
Number |
pipe
Size |
Orifice
Size |
Flow Factor
Kv
|
Minimum
pressure |
Maximum Operating Pressure
(bar) |
BTP |
Material |
Constr.
Ref. |
VA
Rating |
Coil
|
Housing |
| Inch |
mm |
M³/hr. |
bar |
Hot Water* |
Steam |
bar |
Body |
Seat |
AC |
Type |
| 9130D104 |
3/8 |
16 |
2.6 |
0.5 |
5 |
4 |
40 |
BR |
EPDM |
159 |
36 |
M50-HT |
SQ |
| 9130D154 |
1/2 |
16 |
3.6 |
0.5 |
5 |
4 |
40 |
BR |
EPDM |
159 |
36 |
M50-HT |
SQ |
| 9130D204 |
3/4 |
20 |
5.3 |
0.5 |
5 |
4 |
40 |
BR |
EPDM |
159 |
36 |
M50-HT |
SQ |
| 9130D254 |
1 |
25 |
8.6 |
0.5 |
5 |
4 |
40 |
CF8 |
EPDM |
159 |
36 |
M50-HT |
SQ |
| 9130D304 |
1 ¼ |
28 |
14.0 |
0.5 |
5 |
4 |
40 |
CF8 |
EPDM |
159 |
36 |
M50-HT |
SQ |
| 9130D354 |
1 ½ |
34 |
17.3 |
0.5 |
5 |
4 |
40 |
CF8 |
EPDM |
159 |
36 |
M50-HT |
SQ |
| 9130D504 |
2 |
45 |
30.5 |
0.5 |
5 |
4 |
40 |
CF8 |
EPDM |
159 |
36 |
M50-HT |
SQ |
|
| * Hot water at 95°C only. |
| |
| ELECTRICAL REFERENCE |
| Coil Type |
Power Consumption & Watt Rating |
Class Of
Insulation |
Protection |
| AC |
| VA Inrush |
VA Holding |
| M 50 HT SQ |
50 |
36 |
H |
C |
GP/WP IP-67 |
| M 50 HT RD |
50 |
36 |
H |
C |
GP/WP IP-67 |
| M 50 HT
FLP IIB/FLP IIC |
50 |
36 |
H |
C |
IS 2148 Group IIA, IIB, IIC
IS 13947 Part I IP-67
IS 4012 Dustproof/ IS 4013 Dustlight |
|
|
|
| |
| EXAMPLE : |
| A valve is required to pass 400 Kg/h (Qm) of saturated steam at inlet pressure of 7 bar (g) ∆P of 0.5 bar : What is the Kv? |
| |
| SOLUTION : |
| Read the steam graph to find the graph factor (Fg) and use the formula : Kv=QM/Fg = 400/45 = 8.5 |
| |
| NOTE : |
| Absolute pressure = gauge pressure plus atmospheric pressure of 1.033 bar. In most system it is desirable to keep the pressure drop to a minimum. Never use a ∆P greater than 50% of the absolute inlet pressure because excessive pressure drop cause irregular flow. |
| |
| Note: |
Technical specifications details & dimensions are subject to change without prior notice.
Dimensions in the table are approximate subject to final confirmation by AVCON. |
| |
|
|
|
|