Home > Solenoid Valves > 2 Way Solenoid Valves for Steam & Hot Water > 9130H |
|
| |
2/2-Way Pilot Operated, Piston Type, Solenoid Valves
For steam and hot water application, upto 9 bar pressure,
Normally Closed, Energised To Open |
DATA SHEET
9130 H |
|
| |
|
| SPECIFICATIONS : |
| Sizes |
10 mm (3/8") to 50 mm (2"). |
| End Connections |
Standard-BSP. |
| Construction -Body |
Upto 20mm (3/4") Brass forged IS 6912 and above in
SS ASTM A351 Gr. CF8. |
| -Seat |
Standard-PTFE.
Optional-PTFE backed by EPDM. |
| Differential Pressure |
From 1.4 to 9 bar (See table). |
| Coil Voltage |
Standard-230-volts, 50Hz AC.
Optional-Any Standard AC voltage range. |
| Coil Insulation and Temperature |
Ambient upto 42°C.
Class 'H' insulated upto 155°C.
Class 'C' insulated upto 180° C. |
Coil rating
|
Continuously rated. |
| Enclosure |
Standard-General Purpose SQ. moulded coil upto IP-20,
Optional- Weatherproof SQ. moulded coil upto IP-67,
Flameproof Round coil upto FLP IIB/ FLP IIC. |
| Approvals |
CIMFR Dhanbad. |
| Fluids |
Steam temp. upto 180°C.
Hot water temp. upto 95°C. |
| Sales Point |
Pilot operated, standard valve for high pressure steam application. |
| Application |
Steaming equipment, textile, processing equipment, laundry equipment, kitchen equipment and others. |
|
 |
| Note |
Not suitable for back pressure working from outlet side.
Hot water temperature limited upto 95°C only.
Not suitable for wet steam:
Not available in Normally Open design.
Manual override not available.
Not available in DC.
For application where the steam pressure is below 4 bar, we recommend use of 9130D design valves, with EPDM diaphragm
(Refer to data sheet 9130D).
USE OF FILTER IN THE INLET SIDE IS HIGHLY RECOMMENDED. |
|
|
|
 |
SPECIFICATION TABLE
2/2 WAY NORMALLY CLOSED |
Catalogue
Number |
pipe
Size |
Orifice
Size |
Flow Factor
Kv |
Minimum
pressure |
Maximum Operating Pressure
(bar) |
BTP |
Material |
Constr.
Ref. |
VA
Rating |
Coil |
Housing |
| Inch |
mm |
M³/hr. |
bar |
Hot Water* |
Steam |
bar |
Body |
Seat |
AC |
Type |
| 9130H104 |
3/8 |
16 |
2.6 |
1.4 |
9 |
9 |
40 |
BR |
PTFE |
160 |
36 |
M50-HT |
SQ |
| 9130H154 |
1/2 |
16 |
3.6 |
1.4 |
9 |
9 |
40 |
BR |
PTFE |
160 |
36 |
M50-HT |
SQ |
| 9130H204 |
3/4 |
20 |
5.3 |
1.4 |
9 |
9 |
40 |
BR |
PTFE |
160 |
36 |
M50-HT |
SQ |
| 9130H254 |
1 |
25 |
8.6 |
1.4 |
9 |
9 |
40 |
CF8 |
PTFE |
160 |
36 |
M50-HT |
SQ |
| 9130H304 |
1¼ |
28 |
14.0 |
1.4 |
9 |
9 |
40 |
CF8 |
PTFE |
160 |
36 |
M50-HT |
SQ |
| 9130H354 |
1½ |
34 |
17.3 |
1.4 |
9 |
9 |
40 |
CF8 |
PTFE |
160 |
36 |
M50-HT |
SQ |
| 9130H504 |
2 |
45 |
30.5 |
1.4 |
9 |
9 |
40 |
CF8 |
PTFE |
160 |
36 |
M50-HT |
SQ |
|
| * Hot water at 95°C only. |
| |
| ELECTRICAL REFERENCE |
| Coil Type |
Power Consumption & Watt Rating |
Class Of
Insulation |
Protection |
| AC |
| VA Inrush |
VA Holding |
| M 50 HT SQ |
50 |
36 |
H |
C |
GP/WP IP-67 |
| M 50 HT RD |
50 |
36 |
H |
C |
GP/WP IP-67 |
M 50 HT
FLP IIB/FLP IIC |
50 |
36 |
H |
C |
IS 2148 Group IIA, IIB, IIC
IS 13947 Part I IP-67
IS 4012 Dustproof/ IS 4013 Dustlight |
|
|
| DIMENSIONS ( IN MM ) |
Catalogue
Number |
Pipe
Size |
Constr.
Ref. |
A |
B |
C |
D |
Weight
(Approx.) |
| Inch |
kgs.* |
| 9130H104 |
3/8 |
160 |
65 |
28 |
129 |
68 |
1.375 |
| 9130H154 |
1/2 |
160 |
65 |
28 |
129 |
68 |
1.375 |
| 9130H204 |
3/4 |
160 |
80 |
32 |
134 |
79 |
1.805 |
| 9130H254 |
1 |
160 |
95 |
41 |
139 |
93 |
2.295 |
| 9130H304 |
1 ¼ |
160 |
100 |
43 |
144 |
106 |
2.575 |
| 9130H354 |
1 ½ |
160 |
118 |
43 |
144 |
117 |
3.080 |
| 9130H504 |
2 |
160 |
137 |
58 |
151 |
135 |
4.495 |
|
| |
CONSTRUCTION REF.NO.: 160

| TEMPERATURE TABLE FOR SATURATED STEAM UNDER GAUGE PRESSURE |
| Pressure (bar) |
Temp (°C) |
Pressure (bar) |
Temp (°C) |
| 0.5 |
111 |
6 |
165 |
| 1 |
120 |
7 |
170 |
| 1.5 |
127 |
8 |
175 |
| 2 |
134 |
9 |
180 |
| 2.5 |
139 |
10 |
184 |
| 3 |
144 |
11 |
188 |
| 3 |
148 |
12 |
191 |
| 4 |
152 |
13 |
195 |
| 4.5 |
155 |
14 |
198 |
| 5 |
159 |
15 |
200 |
|
 |
Valve fitted with M50 RD GP coil-
General purpose enclosure as per IP-20

Valve fitted with M50 RD coil-
Waterproof metallic enclosure as per IS 13947 Part I IP-67

Valve fitted with M50 FLP IIB / FLP IIC coil-
Flameproof metallic enclosure as perIS/IEC-60079-1-2007 |
|
| |
Catalogue
Number |
Pipe
Size |
Constr.
Ref. |
E (RADIALLY) |
F |
G (APPROX.) |
| Inch |
RD GP |
RD WP |
FLP |
RD GP |
RD WP |
FLP |
RD GP |
RD WP |
FLP |
| 9130H104 |
3/8 |
160 |
66 |
96 |
96 |
57 |
68 |
80 |
120 |
125 |
190 |
| 9130H154 |
1/2 |
160 |
66 |
96 |
96 |
57 |
68 |
80 |
120 |
125 |
190 |
| 9130H204 |
3/4 |
160 |
66 |
96 |
96 |
57 |
68 |
80 |
125 |
130 |
195 |
| 9130H254 |
1 |
160 |
66 |
96 |
96 |
57 |
68 |
80 |
130 |
135 |
200 |
| 9130H304 |
1 ¼ |
160 |
66 |
96 |
96 |
57 |
68 |
80 |
135 |
140 |
205 |
| 9130H354 |
1 ½ |
160 |
66 |
96 |
96 |
57 |
68 |
80 |
135 |
140 |
205 |
| 9130H504 |
2 |
160 |
66 |
96 |
96 |
57 |
68 |
80 |
142 |
147 |
212 |
|
|
|
| |
|
| FLOW CALCULATION GRAPHS FOR SATURATED STEAM : |
| The valve flow coefficient Kv = 1, if 1 cubic meter (m³) water (at 30°C) is passing through the valve per hour with a pressure drop (∆P) of a bar. To select the right valve with certain Kv value, read to steam flow graphs as follows. |
| |
| EXAMPLE : |
| A valve is required to pass 400 Kg/h (Qm) of saturated steam at inlet pressure of 7 bar (g) ∆P of 0.5 bar : What is the Kv? |
| |
| SOLUTION : |
| Read the steam graph to find the graph factor (Fg) and use the formula : Kv=QM/Fg = 400/45 = 8.5 |
| |
| NOTE : |
| Absolute pressure = gauge pressure plus atmospheric pressure of 1.033 bar. In most system it is desirable to keep the pressure drop to a minimum. Never use a ∆P greater than 50% of the absolute inlet pressure because excessive pressure drop cause irregular flow. |
| |
| * Weight with SQ enclosure only, ask AVCON for other weights. |
| |
| Note: |
Technical specifications details & dimensions are subject to change without prior notice.
Dimensions in the table are approximate subject to final confirmation by AVCON. |
| |
|
|
|
|