Home

About Us

Products Newsletter Offshore Capabilities Downloads Contact Us
    Products l Back  
    Hydro Motor Valve , Type HMV DATA SHEET
HMV
   
 FEATURES :                              
  • Slow opening , fast shut-off
  • Robust Construction
  • Economically Priced

OPERATING PRINCIPLE :
Hydro motor valve HMV is normally closed, hydraulically operated safety valve.
When the mains signal is given to an actuator, the internal oil pump builds up the pressure. This oil pressure slowly acts from downward direction on actuator piston. The oil pump switches off as the valve opens completely. The pressure is continuously maintained within the actuator. In event of occurence of drop in pressure while closing the valve, the mains voltage has to be disconnected. After disconnecting the mains signal, the oil pressure is revealed and the valve disc is getting closed within 1 second with the help of closing spring force.
CONSTRUCTION :
Valve Body Aluminium Silicon Alloy or Cast Iron/SG Iron
Valve Disc Aluminium Silicon Alloy
Valve Disc Seal Perbunan/ Polyurethane/Viton
End Connection Flanged to DIN PN 16 or ANSI B 16.5, Class 150 RF
Working Temperature (-)15°C to (+)60°C
Working Pressure 230 milibar to 8 bar
Voltage 230 VAC(+10/-15%),50/60Hz Standard
110 VAC(+10/-15%),50/60Hz Optional
Fluids Natural Gas, LPG in gaseous form,Town gas, Biogas.
 
APPLICATION :
To control and regulate the gas, air flow to burners and other combustion devices. HMV is a unique safety valve that can be supplied for the requiremen of handling higher normal pressure and higher flow where normal Solenoid Valves have limitations.HMV is highly dependable valve to be used on combustion equipment especially in Furnaces, Boilers, Ovens, Blast Furnace and Producer gas installation. gas delivery lines, and oil & gas refineries. etc. where safety requirements are very high.





Opening Time :
HMV .. A, HMV .. G,
~ 5 sec. for NB
~ 8 sec. for 50-65 NB
~ 10 sec. for 80-100 NB
~ 13 sec. for 125 NB

HMV .. H
~ 18 sec. for 50-100 NB
~ 24 sec. for 125-250 vNB

 


SELECTION CHART FOR HYDRO MOTOR VALVE (HMV)
HMV Type Hydro Motor Valve
50 Size mm 40, 50, 65, 80, 100, 125, 150, 200, 250
F
A
End Connections = Flanged to DIN PN 16
= Flanged to ANSI B 16.5, Class 150 RF
20 Inlet pressure 02 = 230 mbar 04 = 400 mbar 05 = 500 mbar
06 = 600 mbar 10 =1000 mbar 15 =1500 mbar
20 = 2000 mbar 24 =2400 mbar 31 =3100 mbar
40 =4000 mbar 60 =6000 mbar 80 =8000 mbar
T5 Mains Voltage T5 = 220 / 240 V, 50 /60 Hz Q6=120V, 50 Hz
M=100 V, 50 /60 Hz, K=24 DC
H Actuator for Higher Inlet Pressure
A Valve Body A = Aluminium Silicon Alloy
G = Cast Iron/ GGG 140
9 Connection Box 9 = With IP54 terminal
6 = With Standard Socket
3 Screw at the inlet and outlet  
D * With flow adjuster  
S * With position indicator  
R * With Holding Relays  
V * With Viton Seal  
(*) Optional Feature, when (*) this letter is dropped, the next letter moves up.
   
 
Products l Back
   
  home l about us l products l newsletter l offshore capabilities l downloads l sitemap l faq l contact us Copyright © 2008 All Rights Reserved