    High Pressure Regulator For Air & Gas DATA SHEET
RG 100/200
   

FEATURES :

  • All metal construction with Nylon inserted Anti Viking PerbunanDiaphragm for Gas, Buna Nit rile for Air No Gland Packing.
  • Non protruding type adjustments Spindle with thrust bearing
    fitted for ease of spring adjustments.
  • Protective cap and locking arrangement which disables
    unauthorized tampering with the set pressure.
  • Internal impulse drilling.
  • Also available with External impulse line with vibration damping
    valve for greater accuracy in outlet pressure.
  • Constant set pressure, (+/-5% of the set range ), irrespective
    of change in inlet pressure and flow.
  • Solid steel construction designed to API Standard.
CONSTRUCTION :
Valve Body Cast steel to ASTM A 216
Body & spring chamber Cast steel to ASTM A 216 Gr. WCB
Spring As per IS 4454 Gr. |||
Spindle Series 400. Burnished & hard chrome plated
Plug Stainless Steel 304
Seat Soft Seat Teflon (Single Seated)
Diaphragm Calendared sheet Nylon inserted Perbunan/Buna Nitrile.
End Connection Screwed to BSP / NPT (F) or Externally Screwed Flanges to ANSI B 16.5, Class 150/300 RF
Working Temperature (-)15°C to (+) 80°C
Inlet Pressure 3 to 10 bar (For RG XX R 100)
6 to 20 bar (For RG XX R 200)
Leakage Class VI on Shut- off
Fluids Natural Gas, LPG in gaseous form, Town Gas, Biogas, Air.
Set Pressure Range Type RG XX R 100 RG XX R 200
  A 0.4 to 4.0 bar 0.4 to 4.0 bar
B 1.5 to 5.0 bar 1.5 to 5.0 bar
C 3.0 to 8.5 bar 3.0 to 8.5 bar
D   5.5 to 12.0 bar
HIGHER SET PRESSURE RANGE IS AVAILABLE

OPERATING PRINCIPLE :
The regulation takes place by means of a spring force by moving the diaphragm and the stem against the gas pressure flowing through the regulator, below the diaphragm assembly.The outlet pressure can be varied by means of adjusting the spring force.

The design offers constant set pressure(±5% of the set point)irrespective of change in inlet pressure and inlet flow.

Also available with external impulse line with vibration damping valve to achieve greater accuracy in outlet pressure.

1

 

 

 

1

 
1
 
DIMENSIONAL DETAILS :
Model Size Dimensions Approx
Weight
Kgs.
Inches mm A B C 0D
RG 15 R 100
RG 15 R 200
1/2" 15 156 84 340 204 18.0
RG 20 R 100
RG 20 R 200
3/4" 20 156 84 340 204 17.7
RG 25 R 100
RG 25 R 200
1" 25 156 84 340 204 17.5
RG 35 R 100
RG 35 R 200

1½"

35 216 95 395 254 34.5
RG 50 R 100
RG 50 R 200
2" 50 216 95 395 254 34.0
1
1
PRESSURE RATIO
LP : HP
CAPACITY FACTOR
"W"
0.96 2.5
0.94 2.0
0.92 1.8
0.91 1.7
0.89 1.6
0.88 1.5
0.86 1.4
0.83 1.3
0.79 1.2
0.73 1.1
0.58 1.0
When the downstream pressure (LP) is greater than half of the upstream pressure (HP) , the maximum flow rate required should be multiplied by a capacity factor "W" obtained by the above table.
SPECIFIC GRAVITY :
Natural Gas 0.62
Town Gas 0.45
LP Gas 1.56
Air 1.0
Note:
Technical specifications details & dimensions are subject to change without prior notice.
Dimensions in the table are approximate subject to final confirmation by AVCON.
   
Products l Back
   